  • Nominal sizes: 7.5 &10 Tons
  • Up to 14.1 IEER / 11.0 EER / 3.4 COP
  • For use with matching RHCYP Models
  • Refrigerant Type: R-454B
Unit of Measure
Items
RPCY2090-Exterior-2_Unbranded

RPCY Commercial Split Achiever® Series Heat Pump

RPCY2090-Exterior-2_Unbranded

RPCY Commercial Split Achiever® Series Heat Pump

RPCY2090-Exterior-2_Unbranded

RPCY Commercial Split Achiever® Series Heat Pump

RPCY2120-Exterior-2_Unbranded

RPCY Commercial Split Achiever® Series Heat Pump

RPCY2120-Exterior-2_Unbranded

RPCY Commercial Split Achiever® Series Heat Pump
Voltage N/A 208 V230 V N/A 460 V N/A 575 V N/A 208 V230 V N/A 460 V
Number of Phases N/A 3
Nominal Cooling Capacity N/A 90000 Btu/h26 kW7.5 TR N/A 90000 Btu/h26 kW7.5 TR N/A 90000 Btu/h26 kW7.5 TR N/A 120000 Btu/h35 kW10 TR N/A 120000 Btu/h35 kW10 TR
IEER N/A 14.1
EER N/A 11.0
Total Capacity N/A 85500 Btu/h N/A 85500 Btu/h N/A 85500 Btu/h N/A 114000 Btu/h N/A 114000 Btu/h
Net Sensible Capacity N/A 62215 Btu/h N/A 62215 Btu/h N/A 62215 Btu/h N/A 84000 Btu/h N/A 84000 Btu/h
Net Latent Capacity N/A 23285 Btu/h N/A 23285 Btu/h N/A 23285 Btu/h N/A 30000 Btu/h N/A 30000 Btu/h
Indoor CFM N/A 2875 ft³/min1357 L/s N/A 2875 ft³/min1357 L/s N/A 2795 ft³/min1319 L/s N/A 4050 ft³/min1911 L/s N/A 4050 ft³/min1911 L/s
Compressor Type N/A Z-Scroll
Number of Compressors N/A 1
Compressor - Rated Load Amperes (RLA) N/A 26.3 A N/A 11 A N/A 9.2 A N/A 26.5 A N/A 14 A
Compressor - Locked Rotor Amperes (LRA) N/A 178.5 A N/A 95.3 A N/A 65 A N/A 255 A N/A 123 A
Number of Fans N/A 1 N/A 1 N/A 1 N/A 2 N/A 2
Fan Motor - Full Load Amperes N/A 5.2 A N/A 3 A N/A 1 A N/A 5.2 A N/A 3 A
Minimum Circuit Ampacity N/A 39 A N/A 17 A N/A 13 A N/A 44 A N/A 24 A
Fuse or HACR Circuit Breaker - Minimum N/A 45 A N/A 20 A N/A 15 A N/A 60 A N/A 30 A
Fuse or HACR Circuit Breaker - Maximum N/A 60 A N/A 25 A N/A 20 A N/A 70 A N/A 35 A
Face Area N/A 32.8 ft²
Rows N/A 2
CFM N/A 5700 ft³/min2690 L/s N/A 5700 ft³/min2690 L/s N/A 5700 ft³/min2690 L/s N/A 11400 ft³/min5380 L/s N/A 11400 ft³/min5380 L/s
Refrigeration Charge N/A 9939 g328.5 oz N/A 9939 g328.5 oz N/A 9939 g328.5 oz N/A 14189 g460 oz N/A 14189 g460 oz
Depth N/A 31 1/8 in N/A 31 1/8 in N/A 31 1/8 in N/A 40 in N/A 40 in
Width N/A 42 11/16 in N/A 42 11/16 in N/A 42 11/16 in N/A 74.268 in N/A 74.268 in
Height N/A 48 13/16 in N/A 48 13/16 in N/A 48 13/16 in N/A 43.989 in N/A 43.989 in
Weight N/A 428 lb194 kg N/A 428 lb194 kg N/A 428 lb194 kg N/A 642 lb291 kg N/A 642 lb291 kg
Shipping Weight N/A 448 lb203 kg N/A 448 lb203 kg N/A 448 lb203 kg N/A 662 lb300 kg N/A 662 lb300 kg
Features N/A
    The RPCY Series commercial split models are engineered for reliable operation and consistent heating and cooling performance. Designed for easy maintenance and serviceability, all access panels can be opened or removed without affecting the structural strength of the unit, helping facilitate easier routine maintenance such as coil cleaning or component inspection. Stamped louvered panels offer 100% protection for the condenser coil, adding to unit performance and reliability.
    Available power options: 208-230V / 3 phase / 60 Hz • 460V / 3 phase / 60 Hz • 575V / 3 phase / 60 Hz
    Limited Warranty (Commercial Applications): Parts – 1 Year • Compressor – 5 Years. Additional extended warranty packages available through ProtectionPlus®.