Ruud Logo Background

CAD/BIM

  • Cooling Efficiency: 15.2 SEER2/11.5 EER2
  • Refrigerant Type: R-454B
  • Nominal Sizes 2 to 5 Tons [7.0 – 17.6 kW]
  • Rated Cooling Capacities: 22.8 to 56 kBTU
  • EcoNet® Enabled: No
  • Compressor Type: Two-Stage Scroll
  • Evaporator Coil Type: MicroChannel
  • Condenser Coil Type: MicroChannel
  • Airflow Type: Convertible
  • Ultra Low NOx Option: No
  • Low NOx Option: No
  • 1-Phase Option: Yes
  • 3-Phase Option: Yes
  • Compatible Thermostat: Single-Stage 24V
  • PlusOnes:
    • PlusOne® Refrigerant Detection System™1- Integrated, patented design providing system protection and homeowner peace-of-mind with low GWP refrigerant monitoring

1Factory installed on 3.5, 4 and 5 ton models. For R-454B equipment with a refrigerant charge less than 3.9 lbs (≈1.8 kg or ≈62.6 oz), a refrigerant detection system is not required by the UL 60335-2-40 standard.

Unit of Measure
Items
RACAYC-Endeavor-Line-Achiever-Plus-Series-Residential-Packaged-Air-Conditioner

RAC(A/X)YC Endeavor® Line Achiever Plus® Series Residential Packaged Air Conditioner

RACAYC-Endeavor-Line-Achiever-Plus-Series-Residential-Packaged-Air-Conditioner

RAC(A/X)YC Endeavor® Line Achiever Plus® Series Residential Packaged Air Conditioner

RACAYC-Endeavor-Line-Achiever-Plus-Series-Residential-Packaged-Air-Conditioner

RAC(A/X)YC Endeavor® Line Achiever Plus® Series Residential Packaged Air Conditioner

RACAYC-Endeavor-Line-Achiever-Plus-Series-Residential-Packaged-Air-Conditioner

RAC(A/X)YC Endeavor® Line Achiever Plus® Series Residential Packaged Air Conditioner

RACAYC-Endeavor-Line-Achiever-Plus-Series-Residential-Packaged-Air-Conditioner

RAC(A/X)YC Endeavor® Line Achiever Plus® Series Residential Packaged Air Conditioner
Voltage N/A 208/230 V N/A 208/230 V N/A 208/230 V N/A 460 V N/A 208/230 V
Frequency N/A 60 Hz
Number of Phases N/A 3 N/A 1 N/A 3 N/A 3 N/A 1
Outdoor Sound Rating N/A 74 dB N/A 74 dB N/A 71 dB N/A 71 dB N/A 71 dB
Refrigerant Charge N/A 47 oz1332 g N/A 47 oz1332 g N/A 53 oz1503 g N/A 53 oz1503 g N/A 53 oz1503 g
Minimum Circuit Ampacity N/A 13 N/A 19 N/A 18 N/A 11 N/A 25
Minimum Overcurrent Protection Device Size N/A 15 N/A 30 N/A 25 N/A 15 N/A 35
Maximum Overcurrent Protection Device Size N/A 15 N/A 30 N/A 25 N/A 15 N/A 35
Overcurrent Protection [Min] N/A
Shipping Weight N/A 367 lb166 kg N/A 367 lb166 kg N/A 436 lb198 kg N/A 436 lb198 kg N/A 436 lb198 kg
Nominal Cooling Capacity N/A 24200 Btu/h7.09 kW N/A 24200 Btu/h7.09 kW N/A 35800 Btu/h10.49 kW N/A 35800 Btu/h10.49 kW N/A 35800 Btu/h10.49 kW
EER2 N/A 11.5 N/A 11.5 N/A 12 N/A 12 N/A 11.5
SEER2 N/A 15.2 N/A 15.2 N/A 16 N/A 16 N/A 15.2
Nominal CFM N/A 800 ft³/min378 L/s N/A 800 ft³/min378 L/s N/A 1200 ft³/min566 L/s N/A 1200 ft³/min566 L/s N/A 1200 ft³/min566 L/s
AHRI Rated CFM N/A 815 ft³/min385 L/s N/A 815 ft³/min385 L/s N/A 1200 ft³/min566 L/s N/A 1200 ft³/min566 L/s N/A 1200 ft³/min566 L/s
AHRI Net Cooling Capacity N/A 22800 Btu/h6.68 kW N/A 22800 Btu/h6.68 kW N/A 34200 Btu/h10.02 kW N/A 34200 Btu/h10.02 kW N/A 34200 Btu/h10.02 kW
Net Sensible Cooling Capacity N/A 16600 Btu/h4.86 kW N/A 16600 Btu/h4.86 kW N/A 25800 Btu/h7.56 kW N/A 25800 Btu/h7.56 kW N/A 25800 Btu/h7.56 kW
Net Latent Cooling Capacity N/A 6800 Btu/h1.99 kW N/A 6800 Btu/h1.99 kW N/A 9200 Btu/h2.7 kW N/A 9200 Btu/h2.7 kW N/A 9200 Btu/h2.7 kW
Net System Power N/A 1.92 kW N/A 1.98 kW N/A 2.86 kW N/A 2.86 kW N/A 2.94 kW
High Temp. Rating N/A
High Temp. Rating - System Power N/A
High Temp. Rating - System Power - COP N/A
Low Temp. Rating N/A
Low Temp. Rating - System Power N/A
Low Temp. Rating - System Power - COP N/A
HSPF2 N/A
Type N/A Double-Stage Scroll
No. Stages N/A 1
Fin Type N/A Louvered
Tube Type N/A MicroChannel
MicroChannel Depth N/A 0.709 in18 mm N/A 0.709 in18 mm N/A 0.472 in12 mm N/A 0.472 in12 mm N/A 0.472 in12 mm
Face Area N/A 9.77 ft²0.91 m² N/A 9.77 ft²0.91 m² N/A 16.26 ft²1.51 m² N/A 16.26 ft²1.51 m² N/A 16.26 ft²1.51 m²
Rows N/A 1
FPI N/A 23
Fin Type N/A Louvered
Tube Type N/A MicroChannel
MicroChannel Depth N/A 1 in25.4 mm
Face Area N/A 3.54 ft²0.33 m² N/A 3.54 ft²0.33 m² N/A 4 ft²0.37 m² N/A 4 ft²0.37 m² N/A 4 ft²0.37 m²
Rows N/A 1
FPI N/A 20
Refrigerant Control N/A TX Valves
Drain Connection No. N/A 1
Drain Connection Size N/A 0.75 in19.05 mm
Type N/A Propeller
No. Used N/A 1
Diameter N/A 22 in558.8 mm
Drive Type N/A Direct
No. Speeds N/A 1
CFM N/A 2500 ft³/min1180 L/s N/A 2500 ft³/min1180 L/s N/A 3250 ft³/min1534 L/s N/A 3250 ft³/min1534 L/s N/A 3250 ft³/min1534 L/s
No. Motors N/A 1
Horsepower N/A 1/6 hp N/A 1/6 hp N/A 1/3 hp N/A 1/3 hp N/A 1/3 hp
Motor RPM N/A 825
Type N/A FC Centrifugal
No. Used N/A 1
Diameter N/A 10x9 in254x229 mm N/A 10x9 in254x229 mm N/A 12x9 in305x229 mm N/A 12x9 in305x229 mm N/A 12x9 in305x229 mm
Drive Type N/A Direct
No. Speeds N/A Multiple
No. Motors N/A 1
Motor RPM N/A 1050
Motor Frame Size N/A 48
Type N/A Field Supplied
Furnished N/A No
No. Filters N/A 1
Recommended Size N/A 1x24x24 in25x610x610 mm
Depth N/A 50 11/16 in
Width N/A 47 1/2 in
Height N/A 35 15/16 in N/A 35 15/16 in N/A 41 in N/A 41 in N/A 41 in
N/A
  • Two-Stage Scroll Compressors on all models: Modulates between two capacity settings — 67% and 100% — providing more precise temperature control, lower humidity and greater efficiency in comparison to single stage compressors. It uses 70% fewer moving parts which also increases efficiency and reliability
  • PlusOne® Diagnostics1: The Rheem Contractor App and built-in EcoNet® & Bluetooth®2 Technolog, makes monitoring, troubleshooting and repairing the product easier than ever before
  • Installation Commissioning via Bluetooth® Technology: Seamless final install step without DIP switch configuration using the Rheem Contractor App.
  • On-demand dehumidification: Available through EcoNet® thermostat superior performance with less refrigerant charge and less weight than conventional copper tube/aluminum fin coils. All aluminum construction has superior protection against formicary corrosion and aluminum tube rubbing potential. It is easier to clean and has a more robust surface.
  • Constant CFM Motor: Truly variable speed technology allows for ultimate humidity control, quieter sound levels and yearround energy savings
  • Dedicated heating speeds: Maintain consistent performance via Constant CFM motor to keep temp rise at a comfortable level
  • Thermal Expansion Valves: Standard on all models for precise superheat control, reliability, and energy efficiency at all operating conditions
  • High and low Pressure Control: Standard on all models for refrigerant component protection and reliability
  • Filter Drier: Standard on all models
  • 100% Factory Run Tested
  • Stainless Steel Heat Exchanger: Available as factory installed option for better corrosion resistance
  • PlusOne® Ignition System: Proven Direct Spark Ignition System (DSI) for reliability and longevity
  • PlusOne® Refrigerant Detection System™3: An integrated one-box, patented design featuring the A2L sensor and mitigation board, offering easier commissioning with a single component and simplified wiring configuration, compatibility with any 24V thermostat application and system protection by automatically pausing outdoor unit operation – if excess refrigerant is detected
  • Rugged Base Rail: For improved installation and handling. Easily Accessible Control Box, Furnace Compartment and Slide-Out Blower Section: Allows for installability and serviceability
  • Side and Down Discharge Options Available: All models are shipped ready for horizontal applications
  • Double Sloped Evaporator Coil Drain Pan: Allows for complete water removal from the unit—contributing to improved indoor air quality
  • Louvered Condenser Compartment: Protects the coil against yard hazards and/or weather extremes
  • Supply and Return Air Openings: Feature a one-inch-tall flange to prevent water migration into the ductwork
  • Designing for Sustainability with Low GWP: For 2025, the Environmental Protection Agency (EPA) has set a global warming potential (GWP) limit of 700 for refrigerant used in heating and cooling systems. This new requirement will result in a 78%4 lower GWP than previous-generation refrigerants with only minimal changes to system installation. For us, this is another step toward our continued sustainability goal of reducing greenhouse gas emissions, while still delivering an exceptional level if energy efficient, dependable comfort

1Bluetooth functionality applies to the heating section only. 2The BluetoothR word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by RheemR is under license. Other trademarks and trade names are those of their respective owners. 3Factory installed on 3.5, 4 and 5 ton models. For R-454B equipment with a refrigerant charge less than 3.9 lbs (≈1.8 kg or ≈62.6 oz), a refrigerant detection system is not required by the UL 60335-2-40 standard. 4When comparing the GWP of R-454B to R-410A refrigerant.
Weight N/A 163 kg359 lb N/A 163 kg359 lb N/A 194 kg428 lb N/A 194 kg428 lb N/A 194 kg428 lb