Ruud Logo Background

CAD/BIM

Rheem Commercial Classic® Series Package Gas Electric Unit

  • RKNL-B Series
  • ASHRAE 90.1-2010 Compliant Models
  • Unit of Measure

    Voltage

    N/A 208 V230 V

    Number of Phases

    N/A 3

    Frequency

    N/A 60 Hz

    Ignition System

    N/A Electric

    Drive Package

    N/A VFD Belt Drive

    Future Technical Variations

    N/A ClearControl™ (DDC) with VFD

    Gross Cooling Capacity

    N/A 244000 Btu/h

    EER

    N/A 10.8

    IEER

    N/A 12.2

    Nominal CFM

    N/A 8000 ft³/min

    AHRI Rated CFM

    N/A 7725 ft³/min

    AHRI Net Cooling Capacity

    N/A 228000 Btu/h

    Net Sensible Cooling Capacity

    N/A 165600 Btu/h

    Net Latent Cooling Capacity

    N/A 62400 Btu/h

    Net System Power

    N/A 21.11 kW

    Outdoor Sound Rating

    N/A 91 dB

    Fin Type

    N/A Louvered

    Recommended Size

    N/A 2 x 25 x 20 in

    Refrigerant Charge (Sys. 1/Sys. 2)

    N/A 11397/9384 g402/331 oz

    Weight

    N/A 2289 lb

    Shipping Weight

    N/A 2415 lb

    Heating Input (1st Stage)

    N/A 150000 Btu/h

    Heating Input (2nd Stage)

    N/A 300000 Btu/h

    Heating Output (1st Stage)

    N/A 121500 Btu/h

    Heating Output (2nd Stage)

    N/A 243000 Btu/h

    Temperature Rise Range (1st Stage)

    N/A 15 to 45 ºF

    Temperature Rise Range (2nd Stage)

    N/A 15 to 45 ºF

    No. Burners

    N/A 12

    No. Stages

    N/A 2

    Gas Connection Pipe

    N/A 0.75 in

    Type

    N/A Scroll

    No. Stages

    N/A 2

    Tube Type

    N/A Rifled

    Tube Size

    N/A 0.375 in

    Face Area

    N/A 53.3 ft²

    Rows

    N/A 2

    FPI

    N/A 22

    Fin Type

    N/A Louvered

    Tube Type

    N/A Rifled

    Tube Size

    N/A 0.375 in

    Face Area

    N/A 26.67 ft²

    Rows

    N/A 3

    FPI

    N/A 13

    Refrigerant Control

    N/A TX Valves

    Drain Connection No.

    N/A 1

    Drain Connection Size

    N/A 1 in

    Type

    N/A Propeller

    No. Used

    N/A 6

    Diameter

    N/A 24 in

    Drive Type

    N/A Direct

    No. Speeds

    N/A 1

    CFM

    N/A 19800 ft³/min

    No. Motors

    N/A 6

    Horsepower

    N/A 1/3 hp

    Motor RPM

    N/A 1075

    Type

    N/A FC Centrifugal

    No. Used

    N/A 2

    Diameter

    N/A 18 x 9 in

    Drive Type

    N/A Belt (Adjustable)

    No. Speeds

    N/A Multiple

    No. Motors

    N/A 1

    Horsepower

    N/A 5 hp

    Motor RPM

    N/A 1725

    Motor Frame Size

    N/A 184 in

    Type

    N/A Disposable

    Furnished

    N/A Yes

    No. Filters

    N/A 8

    Depth

    N/A 85 29/32 in

    Width

    N/A 152 1/16 in

    Height

    N/A 57 in

    N/A

    • R-410A HFC refrigerant.
    • Complete factory charged, wired and run tested.
    • Scroll compressors with internal line break overload and high-pressure protection.
    • Dual stage compressors.
    • Convertible airflow – vertical downflow or horizontal sideflow.
    • TXV refrigerant metering system on each circuit.
    • High Pressure and Low Pressure/Loss of charge protection standard on all models.
    • Solid Core liquid line filter drier on each circuit.
    • Single slab, single pass designed evaporator and condenser coils facilitate easy cleaning for maintaining high efficiencies.
    • Cooling operation up to 125 degree F ambient.
    • Foil faced insulation encapsulated throughout entire unit minimizes airborne fibers from the air stream.
    • Hinged major access door with heavy-duty gasketing, 1/4 turn latches and door retainers.
    • Slide Out Indoor fan assembly for added service convenience.
    • Powder Paint Finish meets ASTMB117 steel coated on each side for maximum protection. G90 galvanized.
    • Base pan with drawn supply and return opening for superior water management.
    • Forkable base rails for easy handling and lifting.
    • Single point electrical connections.
    • Internally sloped slide out condensate pan conforms to ASHRAE 62 standards.
    • High performance belt drive motor with variable pitch pulleys and quick adjust belt system.
    • Permanently lubricated evaporator, condenser and gas heat inducer motors.
    • Condenser motors are internally protected, totally enclosed with shaft down design.
    • 2 inch filter standard with slide out design.
    • Two stage gas valve and direct spark ignition.
    • Tubular heat exchange for long life and induced draft for efficiency and reliability.
    • Solid state furnace control with on board diagnostics.
    • 24 volt control system with resettable circuit breakers.
    • Colored and labeled wiring.
    • Copper tube/Aluminum Fin coils.
    • Factory Installed Direct Digital Control (DDC) and sensors which can connect to LonWorks™ or BACnet® BAS systems for remote monitoring and control.
    • (-H) Models with Variable Frequency Drive (VFD) meet ASHRAE 90.1-2010 and California Title 24