Print Back
Unit of Measure

Specifications

Nominal Size

N/A 120000 Btu/h35.2 kW10 TR

Nominal CFM

N/A 4000 ft³/min

Rated E.S.P.

N/A 0.3

Motor Horsepower - Standard (1725 RPM)

N/A 2 hp

Motor Horsepower - Optional (1725 RPM)

N/A 2 hp3 hp

Blower Diameter

N/A 12 in

Blower Width

N/A 12 in

Blower Shaft Size

N/A 3/4 in

Motor Sheave Size (1725 RPM)

N/A AVL40

Belt Type and Size

N/A A-52

Coil Face Area

N/A 12.6 ft²

Coil Tube Diameter

N/A 3/8 in

Coil Rows Deep

N/A 4 in

Fins Per Inch

N/A 15

Refrigerant Control—Thermal Expansion Valves

N/A CBBIZE-6-GA

Refrigerant Control—Thermal Expansion Valves No.

N/A 2

Filter Size

N/A Field Installed

Cabinet - Finish

N/A Powder Coat

Cabinet - Sheet Metal

N/A Galvanized

Gauge - Top

N/A 18 in

Gauge - Sides

N/A 16 in

Gauge - Bottom

N/A 18 in

Gauge - Doors and Covers

N/A 20 in

Voltage

N/A 208/230 VAC

Frequency

N/A 60 Hz

Number of Phases

N/A 3

Weight

N/A 447 lb

Shipping Weight

N/A 513 lb

Dimensions

Depth

N/A 52 in

Width

N/A 52 in

Height

N/A 27 in

Features

N/A

  • CABINET—Powder coat painted. Matching discharge plenums and decorative supply and return air grilles are available for use when units are to be installed within conditioned space.
  • MOTOR—Inherently protected motors are mounted inside of insulated cabinet to reduce motor noise. A choice of motor horsepowers and drive combinations are available to allow you to meet specified CFM at various static pressures up to 2" [.498 kPa] external static pressure.
  • LOW PROFILE—Allows for horizontal installation in most standard drop ceiling applications, and the movement of units through most standard doorways for addition or replacement work.
  • THERMAL EXPANSION VALVES—Standard all models.
  • FILTERS—One inch [25 mm] throwaway filters are standard, but filter racks are designed to accept either one inch [25 mm] or two inch [51 mm] filters.
  • EVAPORATOR COIL—Two circuit, interlaced row split coils are constructed with copper tubes and aluminum fins mechanically bonded to the tubes for maximum heat transfer capabilities. All coil assemblies are leak tested up to 450 PSIG [3100 kPa] internal pressure prior to installation into units.
  • REFRIGERANT CONNECTIONS—Field piping connections are made through a fixed post between two side access panels on either side of the unit. Allows flexibility to meet most field conditions as well as full accessibility after the installation is complete. Units may be used with two straight cool condensing units or single circuit manifolded in the field using the copper fittings shipped with each unit. The RHGM Air Handler has not been tested, rated or certified to operate with dual remote heat pumps.
  • DRAIN PAN—The galvanized steel drain pan is designed to trap condensate in either vertical or horizontal installations. Condensate drain connections are located on both sides of the unit allowing complete flexibility to meet most field conditions.
  • SERVICE ACCESS—Two removable panels on top and each side of the unit are easily removed for access to motors, blowers, sheaves, and filters.
  • HORIZONTAL OR VERTICAL—All models are designed for either application and can be installed in either position as supplied from the factory.
  • TESTING—All units are run tested at the factory prior to shipment. Units are shipped with a holding charge of nitrogen.
  • HEAT PUMP—The RHCLP Air Handler is designed for heat pump applications. It has two TX valves with internal check valves that allow reverse flow to occur, providing superior control during heating and cooling cycles. The RHCLP Air Handler has been rated and certified to operate with matching size RPCL heat pumps.