Print Back
Unit of Measure

Specifications

Voltage

N/A 460 V

Number of Phases

N/A 3

Frequency

N/A 60 Hz

Drive Package

N/A VFD Belt Drive

Future Technical Variations

N/A ClearControl™ VFD, featuring HumidiDry™Technology

Gross Cooling Capacity

N/A 188000 Btu/h

EER

N/A 11

IEER

N/A 14.2

Nominal CFM

N/A 6000 ft³/min

AHRI Rated CFM

N/A 5900 ft³/min

AHRI Net Cooling Capacity

N/A 172000 Btu/h

Net Sensible Cooling Capacity

N/A 125700 Btu/h

Net Latent Cooling Capacity

N/A 46300 Btu/h

Net System Power

N/A 15.64 kW

Outdoor Sound Rating

N/A 91 dB

Fin Type

N/A Louvered

Recommended Size

N/A 2 x 25 x 20 in

Refrigerant Charge (Sys. 1/Sys. 2)

N/A 8477/5982 g299/211 oz

Weight

N/A 1906 lb

Shipping Weight

N/A 2032 lb

Compressor

Type

N/A Scroll

No. Stages

N/A 2

Outdoor Coil

Tube Type

N/A Rifled

Tube Size

N/A 0.375 in

Face Area

N/A 53.3 ft²

Rows

N/A 1

FPI

N/A 22

Fin Type

N/A Louvered

Indoor Coil

Tube Type

N/A Rifled

Tube Size

N/A 0.375 in

Face Area

N/A 26.67 ft²

Rows

N/A 2

FPI

N/A 18

Refrigerant Control

N/A TX Valves

Drain Connection No.

N/A 1

Drain Connection Size

N/A 1 in

Re-Heat Coil

Fin Type

N/A Louvered

Tube Type

N/A MicroChannel

MicroChannel Depth

N/A 0.709 in

Face Area

N/A 19.9 ft²

Rows

N/A 1

FPI

N/A 23

Outdoor Fan

Type

N/A Propeller

No. Used

N/A 4

Diameter

N/A 24 in

Drive Type

N/A Direct

No. Speeds

N/A 1

CFM

N/A 16000 ft³/min

No. Motors

N/A 4

Horsepower

N/A 1/3 hp

Motor RPM

N/A 1075

Indoor Fan

Type

N/A FC Centrifugal

No. Used

N/A 2

Diameter

N/A 18 x 9 in

Drive Type

N/A Belt (Adjustable)

No. Speeds

N/A Multiple

No. Motors

N/A 1

Horsepower

N/A 3 hp

Motor RPM

N/A 1725

Filter

Motor Frame Size

N/A 56 in

Type

N/A Disposable

Furnished

N/A Yes

No. Filters

N/A 8

Dimensions

Depth

N/A 85 29/32 in

Width

N/A 152 1/16 in

Height

N/A 57 in

Features

N/A

  • R-410A HFC refrigerant.
  • Complete factory charged, wired and run tested.
  • Scroll compressors with internal line break overload and high-pressure protection.
  • Dual stage compressor on all models.
  • Convertible airflow – vertical downflow or horizontal sideflow.
  • TXV refrigerant metering system on each circuit.
  • High Pressure and Low Pressure/Loss of charge protection standard on all models.
  • Solid Core liquid line filter drier on each circuit.
  • Single slab, single pass designed evaporator and condenser coils facilitate easy cleaning for maintaining high efficiencies.
  • Cooling operation up to 125 degree F ambient.
  • Foil faced insulation encapsulated throughout entire unit minimizes airborne fibers from the air stream.
  • Hinged major access door with heavy-duty gasketing, 1/4 turn latches and door retainers.
  • Slide Out Indoor fan assembly for added service convenience.
  • Powder Paint Finish meets ASTMB117 steel coated on each side for maximum protection. G90 galvanized.
  • Base pan with drawn supply and return opening for superior water management.
  • Forkable base rails for easy handling and lifting.
  • Single point electrical connections.
  • Internally sloped slide out condensate pan conforms to ASHRAE 62 standards.
  • High performance belt drive motor with variable pitch pulleys and quick adjust belt system.
  • Permanently lubricated evaporator, condenser and gas heat inducer motors.
  • Condenser motors are internally protected, totally enclosed with shaft down design.
  • 2 inch filter standard with slide out design.
  • 24 volt control system with resettable circuit breakers.
  • Colored and labeled wiring.
  • Copper tube/Aluminum Fin coils.
  • Supplemental electric heat provides 100% efficient heating.
  • Factory Installed ClearControl™ (DDC) and sensors which can connect to LonWorks™ or BACnet® BAS systems for remote monitoring and control.
  • Variable Frequency Drive (VFD).
  • HumidiDry™ Dehumidification System.